Specifications of Transformer Oil (IEC 296)
|
Uninhibited Oil |
Inhibited Oil |
Test Method |
||||||||
I |
II |
III |
IA |
IIA |
III A |
||||||
appearance |
Clear, no suspended matter and precipitation |
Clear, no suspended matter and precipitation |
|
||||||||
Density (30°C) Max. |
895 |
895 |
ISO 3675 |
||||||||
40°C Max. |
16.5 |
11.0 |
3.5 |
16.5 |
11.0 |
3.5 |
|
||||
-15°C Max. |
800 |
- |
- |
800 |
- |
- |
|||||
-30°C Max. |
- |
1800 |
- |
- |
1800 |
- |
|||||
-40°C Max. |
- |
- |
150 |
- |
- |
110 |
|||||
Flashing point (close cup) Min. |
140 |
130 |
95 |
140 |
130 |
95 |
ISO 2719 |
||||
Pour point Max. |
-30 |
-45 |
-60 |
-30 |
-45 |
-60 |
ISO 3016 |
||||
The neutralization value after oxidation Max. |
0.40 |
- |
|
||||||||
Under slung fat lute after oxidation Max. |
0.10 |
- |
|
||||||||
Volatility acid no. 0.28 Min. |
|
|
120 |
|
|
||||||
Water content Delivery in bulk Max. |
|
IEC 733 |
|||||||||
30 |
30 |
|
|||||||||
Delivery in drum Max. |
40 |
40 |
|
||||||||
Breakdown voltage Untreated oil Min |
|
ICE 156 |
|||||||||
30 |
30 |
|
|||||||||
Treated oil Min. |
50 |
10 |
|
||||||||
dielectric loss factor (90°C) Min. |
0.005 |
0.005 |
IEC 247 |